USER INSTRUCTIONS StartupGuideLogix 3400IQ Digital Positioner FCD LGENIM3403-00
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 MANUFAC_ID. Do not include the ‘0x’ hexadecimal identifier.
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 In the Download Configuration window, click the D
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Transducer Block (FVPTB) NOTE: To view the transducer blo
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 L13 on of the Logix 3400IQ digital positioner is
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 AA. MODE_BLK: TARGET must have OOS selected to edit paramet
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 • Actuator Style: Check this box only if the posi
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 STROKE_ENG: Stoke length of valve. This value is used to c
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Stroke Characterization In addition to three pre-
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Characterization Procedure The following procedure outline
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 6. Activate the custom curve by selecting Custom
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Scope This manual is provided for those users unfamiliar w
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Logix 3400IQ Digital Positioner Calibration Re-Cal Button:
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Pressure Calibration: To perform a pressure calib
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Controlling the Valve The Logix 3400IQ digital positioner
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 (NormalShed_NormalReturn is the typical setting.)
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Configuring the FF Network The big advantage to an FF netw
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 window and change the value in the Loop Time box.
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 ABCA. Download status bar B. Ensure the NI Card is selected
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 AO Block: The AO block must be put into Cascade
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Initiating a Valve Signature A feature of the Logix 3400IQ
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 RAMP_RATE* Desired rate (% per Minute) for ramp
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 FOUNDATION fieldbus Basics The FOUNDATION fieldb
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Signature Procedure The following steps are an example of
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 12. Write value to the Logix 3400IQ digital posi
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 32 Flowserve Corporation Flow Control Division 13
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Hardware Requirements In order to have a FF network the fo
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Getting Started with the NI Configurator The NI
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Figure 3: DD Installation Windows The two sub-directorie
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 ABCDEFGHA. Transducer Block B. Logix 3400IQ Digit
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 Function Blocks With the Logix 3400IQ digital positioner o
Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07 The next four sections detail what parameters mus