31
Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ – 5/15
flowserve.com
Fieldbus
Block Index
Fieldbus
Variable Name
Transducer
Block
Fieldbus
Datatypes
Logix Positioner
Description
Register Type
Fix
Pt
Rd
Variable
Name
R/W
19
POSITIONER_
MASK
XDTB_
MAIN
BIT_STRING 271 U_CHAR NO
Positioner_
Mask
NRW
Status, Alarm, Positioner
Flags
15
MECHANICAL_
MASK
XDTB_MD BIT_STRING 272 U_CHAR NO
Mechanical_
Mask
NRW
Status, Alarm, Mechanical
Flags
14
ELECTRONIC_
MASK
XDTB_
TECH
BIT_STRING 274 U_CHAR NO
Electronic_
Mask
NRW
Status, Alarm, Electronic
Flags
22
PRESSURE_
MASK
XDTB_
TECH
BIT_STRING 275 U_CHAR NO
Pres
-
sure_Mask
NRW
Status, Alarm, Pressure
Flags
16
INNERLOOP_
MASK
XDTB_
TECH
BIT_STRING 276 U_CHAR NO
Inner
Loop_Mask
NRW
Status, Alarm, Inner Loop
Flags
18
OUTERLOOP_
MASK
XDTB_
TECH
BIT_STRING 277 U_CHAR NO
Outer
Loop_Mask
NRW
Status, Alarm, Outer Loop
Flags
20
CONFIGURA
-
TION_MASK
XDTB_
TECH
BIT_STRING 279 U_CHAR NO
Configura-
tion_ Mask
NRW
Status, Alarm, Configuration
Flags
113 BLINK_CODE
XDTB_
MAIN
UNSIGNED 8 283 U_CHAR NO Blink_Code R LED Status Blink Code
Pro Mode Parameters
24
PST_TIME_
BREAKAWAY
XDTB_MD FLOAT 285 U_INT /100
PST_Time
-
Breakaway
NR
Partial Stroke Test breakaway
time
25
PST_PRES
-
SURE_DIFF
XDTB_MD FLOAT 286 U_INT /100
PST_Pres-
sureDiff
R
Partial Stroke Test Pressure
Differential
26
PST_TIME_TO_
TARGET
XDTB_MD FLOAT 287 U_INT /100
PST_TimeTo
-
Target
NR
Partial Stroke Test Time to
Target
27 PST_RESULT XDTB_MD UNSIGNED 8 288 U_CHAR NO PST_Result R
Partial Stroke Test Result
(Pass or Fail)
28
PST_TIME_
LIMIT
XDTB_MD FLOAT 289 U_INT /100
PST_Time
-
Limit
RW Partial Stroke Test Time Limit
29
ACTUATOR_
RATIO
XDTB_MD FLOAT 290 U_INT /100
Actua
-
tion_Ratio
RW Actuation Ratio In Percent
30
ACTUATION_
RATIO_HIGH_
START_LIMIT
XDTB_MD FLOAT 291 U_INT /100
AR_HighStar
-
tLimit
RW
Actuation Ratio High Start
Limit
31
ACTUATION_
RATIO_HIGH_
END_LIMIT
XDTB_MD FLOAT 292 U_INT /100
AR_HighEnd
Limit
RW
Actuation Ratio High End
Limit
32
ACTUA
-
TION_RATIO_
PERCENT_
YELLOW
XDTB_MD FLOAT 293 U_INT /100
AR_Percent
Yellow
NR
Actuation Ration Percent
Yellow
50
SPOOL_
RESPONSE_
TIME
XDTB_MD FLOAT 295 U_INT NO
Spool_
Time_86
NR Spool Response Time
51
SPOOL_START_
LIMIT
XDTB_MD FLOAT 296 U_INT NO SS_LowLimit NRW Spool Start Limit
52
SPOOL_END_
LIMIT
XDTB_MD FLOAT 297 U_INT NO SS_highLimit NRW Spool End Limit
53
SPOOL_
PERCENT
XDTB_MD FLOAT 298 U_INT /100 SS_pctYellow R Spool Percent Yellow
16
VALVE_TRAVEL_
DISTANCE
XDTB_MD FLOAT 301 U_LONG /100
ValveTravel
Distance
R Valve Travel Distance
17
VALVE_TRAVEL_
HIGH_START
XDTB_MD FLOAT 302 U_LONG /100
ValveTravel
-
High Start
RW Valve Travel High Start
18
VALVE_TRAVEL_
HIGH_END
XDTB_MD FLOAT 303 U_LONG /100
ValveTravel
-
High End
RW Valve Travel High End
Kommentare zu diesen Handbüchern