Excessive valve seat leakage
• damaged sealing edges at
valve seat or plug
• foreign particles in seat area
• plug does not close fully
• contact customer services
department or contract partner
• contact customer services
department or contract partner
• refer to 3.1 to 3.5
Leaking stuffing box system
• compression force on packing
too low
• worn packing
• dirty spindle
• damaged spindle
• slightly re-tighten stuffing box packing
Caution: make sure the valve spindles
can still move !
• slightly re-tighten stuffing box packing
Caution: make sure the valve spindles
can still move !
• if the packing does not stop leaking,
contact customer service department
or contract partner
• clean spindle with suitable cleaning
agent
• contact customer services
department or contract partner
• pressing force on seal(s) too
low
• seal(s) defective
• properly re-tighten top or lid nuts
crosswise
• contact customer services
department or contract partner
• medium or flow related damage
• contact customer service department
or contract partner
• power supply to limit switch
interrupted
• limit switch misadjusted
•
check power supply
( voltage, circuit
breakers, connections )
• readjust limit switch; operating
distance see limit switch data sheet
• see maintenance and operating in
structions of positioner manufacturer
If the problem is not solved by taking the above measures, contact the customer services
department or contract partner.