KW941 Pump Power Monitor USER INSTRUCTIONS ENGLISH 71569285 02-12
Page 17 of 24 flowserve.com
6 MAINTENANCE
The KW941 Pump Power Monitor should not require
any routine maintenance outside of wiping down the
front cover occasionally.
It is the plant operator's responsibility to ensure
that all maintenance, inspection and assembly work
is carried out by authorized and qualified personnel
who have adequately familiarized themselves with
the subject matter by studying this manual in detail.
(See also section 1.6.2.)
Before restarting the machine, the relevant
instructions listed in section 5, Setup and Operation
must be observed.
Place a warning sign on the starting device:
"Machine under repair: do not start".
With electric drive equipment, lock the main switch
open and withdraw any fuses. Put a warning sign on
the fuse box or main switch:
"Machine under repair: do not connect".
6.1 Spare parts
No spare parts are needed. The internal fuse is not
meant to be accessed by the customer per CE
requirements. The current sensor (toroid) is robust,
but the leads can be broken off if handled roughly.
Contact your local Flowserve sales representative to
order a new toroid if the leads are damaged. Follow
the procedure in Section 5.5 to calibrate the new
toroid to the KW941 unit.
6.2 Tools required
A flat blade screwdriver, wire cutter, and wire stripper
are all that should be required to work on the wiring
going to the KW941 Pump Power Monitor once it is
installed.
7 FAULTS: CAUSES AND REMEDIES
Troubleshooting
The purpose of this guide is to supply general
information on how to troubleshoot problems related
to startup and operation of the KW941 Pump Power
Monitor. It is intended only as a guide and cannot
cover every situation. If a problem exists that is not
covered by one of the examples, then contact a
Flowserve Sales Engineer or
Distributor/Representative for assistance.
General Guidelines
The KW941 Pump Power Monitor is intended for
use on fixed frequency, steady, non-pulsating
loads. The unit is not intended for use with
variable frequency drives.
When troubleshooting, never swap electronics
from one unit to another. This will cause
operational problems and void any warranty
claim.
It is often helpful to isolate the monitor to
determine if the cause of a problem is internal to
the KW941 or a part of the external wiring
system. By removing all connections except for
the voltage and current sensing toroid, the
problem can normally be isolated to either the
monitor itself or to the external wiring.
Each KW941 has an internal "DEMO MODE"
which can be helpful in verifying the correct
function of the unit. See Section 5.4 for
instructions on how to use this mode.
Typical writing configurations for utilizing alarm
relays are shown in Section 8 as Figures 8.1
and 8.2 for reference.