KW941 Pump Power Monitor USER INSTRUCTIONS ENGLISH 71569285 02-12
Page 6 of 24 flowserve.com
3 DESCRIPTION
3.1 Configurations
The KW941 Pump Power Monitor provides a power
measurement, display and trip-point system to detect
and protect against both UNDERLOAD and
OVERLOAD conditions. The KW941 monitors
MOTOR POWER by sensing both VOLTAGE and
CURRENT. By factoring in motor efficiency, the
KW941 can be scaled to display PUMP POWER. The
adjustable trip-points can be set using power
information provided by the Flowserve Pros+
software for Flowserve pumps.
The KW941 consists of a current sensor and a
Display/Control module. The sensor, through which
one motor power lead passes, normally is located
inside the motor starter panel and provides a sample
of motor current to the Display/Control module. A
voltage sample is provided by a control voltage
transformer (not supplied) located between two of the
three motor power phases. The Display/ Control
module (located outside the starter panel) processes
the current and voltage sample information, contains
the LED display, alarm relays, and provides operator
interface.
Three models of the KW941 Power Monitor are
available based upon the supply voltage at the
customer’s site. The part numbers are listed below:
AY56930B = 110-120v, 60Hz
AY56930C = 220-240v, 50Hz
AY56930D = 220-240v, 60Hz
3.2 Nomenclature
3.2.1 Product Identification Label
3.2.2 Abbreviations
TS = terminal strip
TS1 = terminal strip screw position #1
Jp = jumper
NO = normally open
NC = normally closed
FS = full scale (power)
CR = control relay
MOL = motor overload
3.3 Design of major parts
3.3.1 Enclosure
Material: polycarbonate, with see-through cover.
Protection rating: NEMA 4X / IP66. Use only
certified liquid-tight access hole fittings/conduit
hubs to maintain enclosure protection rating.
Overall dimensions: 182 mm W x 180 mm L x 90
mm H (7.17"W x 7.09"L x 3.54"H).
Mounting hole spacing: 167 mm W x 173 mm H
(6.57"W x 6.81"H).
Mounting screws: 4 mm (#8), quantity of four.
Enclosure can be drilled, sawed or punched for
wiring access holes.
Do not damage the internal
components of the KW941 unit while making access
holes.
3.3.2 Power Requirements
110 Vac Model (110/115/120 nominal Vac),
60 HZ @ 0.100 amps
220 Vac Models (220/230/240 nominal Vac),
50/60 HZ @ 0.05 amps
Fuse: (Internal to TS1 #2 VAC connection, not
user accessible.)
For 110 Vac Models: 200 mA, 125 Vac, Slo
Blo, 5 x 20 mm
For 220 Vac Models: 100 mA, 250 Vac, Slo
Blo, 5 x 20 mm
Power to the KW941 is supplied by a
(customer-supplied) control voltage transformer
connected between two of the three motor power
supply phases. Power may be supplied by an
existing appropriately connected transformer with
adequate capacity. Consult area codes/regulations
for transformer fusing and grounding requirements.