Commissioning – continued –
Examples of configuration settings
1 Example
The following items of equipment are connected to the control unit NRS 1-40.1:
2 Level electrodes NRG 1x-40 for low water level LW 1 and 2
1 Level electrode NRG 1x-41.1 for high water level HW and
1 Temperature transmitter TRV 5-40 for MAX temperature
As only in the temperature transmitter TRV 5-40 the limiter number can be adjusted, the control unit
NRS 1-40.1 has to be configured as follows:
Limiter B1 B2 B3 B4
Function Water level LW 1 Water level LW 2 High water HW Temperature MAX
Set the temperature transmitter TRV 5-40 as limiter 4.
2 Example
The following items of equipment are connected to the control unit NRS 1-40.1:
2 Level electrodes NRG 1x-40 for water level LW 1 and 2 and
1 Temperature transmitter TRV 5-40 for MAX temperature
Limiter B1 B2 B3 B4
Function Water level LW 1 Water level LW 2 Temperature MAX
Set the temperature transmitter TRV 5-40 as limiter 3.
Changing system configuration – continued –
G
Toggle switch white
Code switch G
Limiter
Number
S1 S2
S3 S4 S5 S6 S7 S8
ON ON OFF OFF OFF OFF OFF OFF 1
OFF OFF ON ON OFF OFF OFF OFF 2
OFF OFF OFF OFF ON ON OFF OFF 3
OFF OFF OFF OFF OFF OFF ON ON 4
Factory setting
S9 S10 Communication with control unit
OFF OFF NRS 1-40.1
ON ON NRS 1-40.2