32
Annex
– continued –
Table Node ID
In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own ad-
dress (node ID). This address can be set via a 10-pole code switch Fig.4.
(Factory setting) (Example)
Decommissioning
First unplug the terminal strips , . For this purpose turn the right and left fixing screws in direction
of the arrow until the terminal strip can be removed.
Undo the fixing slide in order to snap out the controller and take it off the supporting rail.
Node ID 1 Node ID 71
S1
ON
1S1
ON
1
S2 OFF 2 S2 OFF 2
S3 OFF 4 S3
ON
4
S4 OFF 8 S4
ON
8
S5 OFF 16 S5 OFF 16
S6 OFF 32 S6 OFF 32
S7 OFF 64 S7
ON
64
S8 S9 S10 Baud rate Cable length
OFF ON OFF 250 kBit/s 125 m
Factory setting
ON ON OFF 125 kBit/s 250 m
OFF OFF ON 100 kBit/s 335 m
ON OFF ON 50 kBit/s 500 m
OFF ON ON 20 kBit/s 1000 m
ON ON ON 10 kBit/s 1000 m
D
ON
123 54678910
D
Toggle switch, white
ON
12
3
54 678910
D
Toggle switch, white
A
B C