AXAIM020-01 (AUTO-48) 3/03 Page 12 of 16
© 2003, Flowserve Corporation, Printed in U.S.A.
BUSwitch
with FOUNDATION
®
Fieldbus Protocol
Installation, Operating and Maintenance Instructions
Flowserve Corporation 1350 N. Mountain Springs Parkway 1978 Foreman Dr.
Flow Control Division Springville, Utah 84663-3004 Cookeville, TN 38501
www.flowserve.com Phone: 801 489 8611 Phone: 931 432 4021
Rel.
Index
Parameter Factory
Default
Description
25 OPERATION Note 1 Configures the piezo/coil element terminals for single coil or dual
coil modes
.
26 OUTPUT_CONFIGUR
ATION
Note 1 Configures the piezo/coil signals to shut-off or remain continuous
after TIME
_
OUT period. Applies to Dual Coil mode only
.
27 ODOMETER This variable counts the transitions from open to closed and
closed to open states. It is reset-able to 0, after maintenanc
e.
28 RESET
_
ODOMETER Resets the ODOMETER counter.
29 FAILURE_RECOVERY Enable/Disable FAILURE_RECOVERY action.1: Act with or
without change in the input, 2: Do not act until a new change in the
inpu
t.
30 RESET
_
TIMEOUT Resets a TIME
_
OUT occurrenc
e.
31 TRANSITION
_
TIME How much time for the last transiti
on.
32 TIME_OUT 10 The time allowed for a transition before the DI associated with the
TIME-OUT Alarm is Activated. Also, the length of the One-Shot
pulse voltage output to the coils in the Dual Coil Operation Mo
de.
33 SOLENOIDE
_
CLOSED SW1 state
34 SOLENOIDE
_
OPEND SW2 st
ate
35 TRANSITION
_
ALARM DI1 state = transition TIME-OUT st
ate
36 EXTERNAL_ALARM DI2 state = It read the status of the Temperature/Pressure Limit
(CN1.12 pin) Data is passed on to DI2.
37 ACTION
_
TIME Time since last command for transition.
Notes:
1. Selected by Factory in accordance with customer PO specifications.
Transducer Block Parameter Specifications
Rel.
Index
Parameter Mnemonic Data
Type
Size Valid
Range
Units Class
1 ST
_
REV Unsigned 16 2 Positive N/A Read
2 TAG
_
DESC Visible String 32 String Data N/A R/W
3 STRATEGY Unsigned 16 2 N/A R/W
4 ALERT
_
KEY Unsigned 8 1 1-255 N/A R/W
5 MODE
_
BLK DS-69 4 N/A R/W
6 BLOCK
_
ERR Bit String 2 N/A
Read
7 UPDATE
_
EVT DS-73 5 N/A
Read
8 BLOCK
_
ALARM DS-72 13 N/A
Read
9 TRANSDUCER_DIRECTORY Unsigned 16
Array
Variable N/A
Read
10 TRANSDUCER
_
TYPE Unsigned 16 2 E
R/W
11 XD
_
ERROR Unsigned 8 1 N/A
Read
12 COLLECTION_DIRECTORY Unsigned 32
Array
Variable
N/A
13 FINAL
_
VALUE
_
D DS-66 2 N/A R/W
14 ACT_FAIL_ACTION Unsigned 8 1 0=Undefined
1=Close
2=Open
3=Last
ER/W
R/W
R/W
15 ACT
_
MAN
_
ID Unsigned 32 4
E