18 CHANNEL 1 for
DI-1
2 for
DI-2
The number of the logical hardware channel that is connected to this I/O
block. This information defines the transducer to be used going to or from the
physical world.
19 FSTATE_TIM
E
The time in seconds from detection of fault of the output block remote setpoint
to the output action of the block output if the condition still exists
.
20 FSTATE_VAL
_D
The preset discrete SP_D value to use when fault occurs. This value will be
used if the I/O option Fault State to value is selected
.
21 BKCAL_OUT_
D
The output value and status provided to an upstream discrete block. This
information is used to provide bumpless transfer to closed loop control.
22 RCAS_IN_D Target setpoint and status provided by a supervisory Host to a discrete
control or output block.
23 SHED
_
OPT *** Defines action to be taken on remote control device timeout.
24 RCAS_OUT_
D
Block setpoint and status provided to a supervisory Host for back calculation
and to allow action to be taken under limiting conditions or mode c
hange.
25 UPDATE
_
EVT This alert is generated by any change to the static data
.
26 BLOCK_ALM The block alarm is used for all configuration, hardware, and connection failure
or system problems in the block. The cause of the alert is entered in the
subcode field. The first alert to become active will set the Active status in the
Status attribute. As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without clearing the Active
status, if the subcode has chang
ed.
*** = NormalShed_NormalReturn