10
Explanatory Notes – continued –
Technical data
Type approval no.
TÜV.WÜL.02-007
EG BAF-MUC 02 05 103881 003
Input/Output
Interface for CAN bus to ISO 11898 CANopen.
Inputs
CAN bus interface with power supply 18-36V DC, short circuit protected.
Analog control input for indicating valve position via feedback potentiometer 1000Ω,
angle of rotation 320°, supply voltage 5V DC.
Voltage input 18-36V AC (50/60 Hz) or DC for external command:
Control OFF, valve CLOSED, intermittent blowdown OFF. With DC protected against
polarity reversal.
Outputs
Four volt-free relay contacts.
Max. contact rating with a switching voltage of 24V AC/DC, 115V AC and 230V AC:
resistive / inductive 4A.
Contact material AgNi 0.15.
Current output 4-20mA as actual value output, max. load 750Ω (optional).
Conductivity measuring range with actual value output 4-20mA
* based at 25°C
Beginning of measuring range End of measuring range
ppm* µS/cm * mA ppm* µS/cm * mA
0.25 0.5 4
10 20 20
50 100 20
100 200 20
250 500 20
500 1000 20
1000 2000 20
3000 6000 20
6000 12000 20
Note
The electrical conductivity is measured in µS/cm. For ppm (parts per million)
use the following conversion:
1µS/cm = 0.5ppm.
Kommentare zu diesen Handbüchern