Flowserve NRGS 16-1 Bedienungsanleitung Seite 12

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 18
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 11
12
NRGS 16-1, NRGS 16-1 S
Use multi-core flexible cable with min. conductor size 1.5 mm² for wiring.
1. Unscrew screws , remove housing cover Fig. 6
2. Unscrew union nuts of cable entry .
The electrode terminal can be turned through +/– 180°.
3. Loosen screw with 17 mm spanner but do not remove. Fig. 7
4. Turn electrode terminal into desired direction (+/– 180°).
5. Tighten screw slightly.
6. Remove terminal strip from board.
7. Connect terminal strip according to wiring diagram, connect PE connection .
8. Insert terminal strip.
9. Replace housing cover , fasten screws and install cable entry.
Fuse supply cables with T 250 mA.
The connection of the switchpoints 2 and 3 must be effected on
site (pump contactor, auxiliary relay)!
Wiring
Tools
Attention
Wiring diagram
Screwdriver for cross head (“Phillips”) screws, size 1
Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680
Open-end spanner 17 mm A. F.
Fig. 8
EE
EE
E
GG
GG
G
FF
FF
F
QQ
QQ
Q
QQ
QQ
Q
MM
MM
M
NN
NN
N
GG
GG
G
EE
EE
E
Mains
Seitenansicht 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 18

Kommentare zu diesen Handbüchern

Keine Kommentare