The measuring range can be switch selected between
≥ 0.5
µ
S/cm and ≥ 10
µ
S/cm
by means of DIP switch :
1. Unscrew screws at the electrode terminal, remove cover , Fig. 6
DIP switch 1– 4 OFF Measuring range ≥ 0.5
µ
S/cm
DIP switch 1–4 ON Measuring range ≥ 10
µ
S/cm
2. Replace cover and fasten screws
Standard setting
Factory setting NRGS 16-1
The compact system is delivered with the following factory settings:
■
Measuring range ≥ 10
µ
S/cm
Switch selection of measuring range
Attention
■
Screwdriver for cross head (“Phillips”) screws, size 1
■
Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680
Tools
LL
LL
L
EE
EE
E
GG
GG
G
GG
GG
G
EE
EE
E
■
Do not damage the electronic components when operating DIP switch.