19
CALIBRATE
AutoCal
AutoCal
Start tune
Actuator?
rotating
OK
TravelCal
Start cal
Perform
normal
LOSE PREV
VALUE?OK?
OK
OK
OK
OK
OK
CALIBRATE
TravelCal
LOSE PREV
VALUE?OK?
IN SERVICE
? Press OK
OK
OK
OK
OK
OK
OK
OK
OK
Direction?
direct
Direction?
reverse
Calibration in
progress
Calibration in
progress
Perform
Factory set
Perform
50%
25%
12%
L
M
S
Actuator?
linear
Actuator
single act
Actuator
single act
IN SERVICE
? Press OK
OK
Set point LO: Use the calibrator set to 4 mA
(or set another value on the display). Press OK.
Set point HI: Use a calibrator of 20 mA
(or set another value on the display). Press OK.
Pressure read out only possible on D3 with built
in pressure sensor.
Pressure LO: Use a supply of 2 bar (30 psi)
(or set another value on the display). Press OK.
Pressure HI: Use a supply of 7 bar (105 psi)
(or set another value on the display). Press OK.
Temp: Calibrate using a known temperature.
Aux input LO: Use the calibrator
and a power supply of 4 mA (or set another
value on the display). Press OK.
Aux input HI: Use a supply of 20 mA
(or set another value on the display). Press OK.
Pot: Potentiometer setting, if its position
relative to the gear segment has been changed.
See Section 8.
Full reset: Resets all the set values.
All these values are set at the
factory before delivery and
should not normally be changed.
CALIBRATE
Perform
CALIBRATE
ExpertCal