Integer
Register
Attribute Description Notes
30014 RO ADC value being output by the position
feedback Hallpot.
Range -32767 to 32767.
30015 RO ADC value being output by the process
temperature thermocouple.
Range 0 to 16383.
30016 RO Flow state register. 0 = liquid choked
1 = liquid non-choked
2 = gas non-choked
3 = gas choked
30017 RO Scaled percentage of full scale process
value for currently selected process
variable.
Range -20 to 120. Fixed scale.
30018 RO Scaled liquid flow in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70465, 70467.
30019 RO Scaled gas flow in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70469, 70471.
30020 RO Scaled P1ISA in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70473, 70475.
30021 RO Scaled P2ISA currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70477, 70479.
30022 RO Scaled dP ISA in currently selected
engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70481, 70483.
30023 RO Scaled process temperature in currently
selected engineering units.
Range 0 to 9999. Variable scale. Scalar
registers are 70485, 70487.
30024 RO Scaled auxiliary input. Range 0 to 9999. Variable scale. Scalar
registers are 70489, 70491.
30025 RO Scaled 4-20 mA command input. Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.
30026 RO Scaled stem position. Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent..
30027 RO Scaled setpoint command. Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.
30028 RO Alarm source register. Bit field/Bit Meaning
0 = Setpoint error
1 = Positioner error
2 = Tripped condition
3 = Unused
4 = Unused
5 = Override status
6 = Sensor malfunction
7 = Hardware malfunction
StarPac II User Interface Manual 30