Integer
Register
Attribute Description Notes
40094 RW Variable number for liquid flow scaling
factor input to be used in flow
calculation.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
liquid flow scaling factor input to the flow
calculation; -1 disables.
40095 RW Variable number for gas flow scaling
factor input to be used in flow
calculation.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the gas
flow scaling factor input to the flow
calculation; -1 disables.
40096 RW Variable number of output No. 1 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on
LCD display; -1 disables.
40097 RW Variable number of output No. 2 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40098 RW Variable number of output No. 3 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40099 RW Variable number of output No. 4 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40100 RW Variable number of output No. 5 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40101 RW Variable number of output No. 6 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40102 RW Variable number of output No. 7 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40103 RW Variable number of output No. 8 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
40104 RW Variable number of output No. 9 to be
displayed on Local display.
Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.
StarPac II User Interface Manual 36