Maintenance
Spare parts
Replace measuring element
The measuring element can be replaced during operation if necessary.
1. Switch off bus supply voltage.
2. Take cover off the terminal box.
3. Disconnect the measuring element .
4. Slacken fixing screws for measuring element. Pull out measuring element.
5. Insert new measuring element and fasten fixing screws.
6. Re-attach measuring element .
7. Replace cover and tighten screw securely.
8. Apply bus supply voltage.
Resistance thermometer type Designation Item Stock code
TRG 5-63
Dimension = 160 mm see Fig.1
Measuring element
1xPt 100
052260
TRG 5-64
Dimension = 160 mm see Fig.1
Measuring element
2xPt 100
052264
TRG 5-65 Measuring element
1xPt 100
052386
TRG 5-66 Measuring element
1xPt 100
052388
TRG 5-67 Measuring element
1xPt 100
1500623
TRG 5-68 Measuring element
2xPt 100
1500624