12
Wiring – continued –
Wiring diagram for CAN bus system – example –
Attention
■ Wire equipment in series. Star-type wiring is not permitted!
■ Connect screens of the bus cables once to the central earthing point (CEP).
■ If two or more system components are connected in a CAN bus system, the first and
the last device must be provided with a terminating resistor of 120 Ω (terminal
C
L
/C
H
). We recommend that you use the URB 2 with a connecting socket equipped with
terminating resistor either as first or as last device.
■ Only one operating and display unit URB 2 may be used per CAN bus network.
■ The CAN bus system must not be interrupted during operation.
In the event of an interruption a malfunction alarm is raised.
■ The operating and display unit URB 2 must not be applied in parallel with the operating,
display & automatic control device SPECTORcontrol.
Basic Settings
Factory setting
Operating & display unit URB 2
The operating and display unit URB 2 unit features the following factory set default values:
■ Node ID: 60
■ Baud rate: 250 kBit/s (125 m cable length)
Fig. 6
Connecting socket with
terminating resistor 120 Ω
Plug with terminating
resistor 120 Ω
Central
earthing point
CEP
Control unit
NRS 1-4x
NRS 2-40
NRR 2-40
LRR 1-40
TRS 5-40
Operating device
URB 2
Level electrode
Conductivity
electrode
NRG x6-4x
LRG xx-4x
Temperature
transmitter
TRV 5-40