Function of keys
Key 1: Reduce value –, browse
Key 3: Increase value +, browse
Key 2 (E): Press briefly: Call up/Execute menu // Continue / Save settings
Key 2 (E): Press longer: Return to menu, cancel input
Key 1 + 3: Press longer: Reset/Delete values (e. g. alarm list + maintenance interval)
LEDs 1 – 3
LED 1: Steam loss
LED 2: Banking-up of condensate
LED 3: Measuring electrode NRG 16-27 defective (short circuits, parting of a cable).
Measuring electrodes NRG 16-19 are not monitored.
Operation, Alarm and Test
Specification of keys and displays
Fig. 6
Key to codes on seven-segment display
Code Meaning
The following codes can appear on the seven-segment display even if no key is being pressed:
SYS System SYS changes with plant temperature in °C
E.01
Error Incorrect configuration due to inadmissible code switch setting
E.02
Error In mode 2 and 7 the settings for banking-up of condensate is not finished
E.03 Error Maintenance interval (6 months) elapsed
C.01 – C.16 Channels 1 - 16
Indication of measuring channel
If the E key is pressed:
HIS History Alarm list detailing old alarms
InT Interval Remaining time of maintenance interval
CAL Calibration Channel calibration in mode 2
dtC (mode 2, 7)
Delta TC Admissible deviation from condensate temperature in steam trap
dtS (mode 1, 6)
Delta TS Admissible deviation from plant temperature
tSt Test LEDs and all segments are illuminated
ALL All channels Channel selection when calibrating / setting
C.01 – C.16 Channels 1 - 16
Indication of measuring channel
don Done Confirmation of input when setting parameters
clr Clear Confirmation of clear command (interval, alarm)