NRA 1-3
Technical Data
Supply voltage
230 V, 50 / 60 Hz
115 V, 50 / 60 Hz optional
Input
16 inputs for measuring electrodes NRG 16-19, NRG 16-27, NRG 16-28
1 input for temperature sensor, e. g. TRG 5-63, temperature sensing element Pt 100
Output
1 volt-free relay contact
Contact material: AgNi 0,15
Max. contact rating for switching voltages of 24 V AC/DC, 115 V AC and 230 V AC:
4 A resistive / inductive
Electrode voltage
12 V
Banking-up of condensate setting
Difference temperature condensate/installation dts 1 K to 100 K, adjustable in steps of 1 K
(mode 1 and 6)
Difference temperature condensate/switchpoint banking-up of condensate dtC 1 K to 100 K,
adjustable in steps of 1 K (mode 2 and 7)
Switchpoint banking-up of condensate 0 °C to 255 °C, adjustable in steps of 5 K (mode 2 and 7)
Indicators and adjustors
1 Three-digit seven-segment LED display, red, for indicating faulty steam traps and status and error
messages
3 LEDs for indicating banking-up of condensate, steam loss and malfunction in measuring electrode
3 Pushbuttons for parameter settings
1 Ten-pole code switch for system configuration
Delay of response
max. 5 sec.
Power consumption
max. 4 W
External fuse
63 mA
Design
NRA 1-3a: for wall mounting
NRA 1-3e: for panel mounting
Protection
NRA 1-3a: IP 65 to EN 60529
NRA 1-3e: Front: IP 65 to EN 60529, back: IP 00
Protection class
NRA 1-3a: 2 (completely insulated)
Max. admissible ambient temperature
55 °C
Enclosure
Material: ABS
Kommentare zu diesen Handbüchern