Basic Settings – continued –
Adjusting sensitivity of response
Press button twice briefly to activate
the line editing mode.
Use buttons and to toggle between
the two settings.
The split-screen window shows which
GESTRA bus devices can be indicated:
■ High-level limiter NRS 1-41
■ Low-level limiter NRS 1-40
■ Level switch NRS 1-42
■ Conductivity controller LRR 1-40
Before commissioning the installation
adjust the response sensitivity of the NRS
1-42.
The response sensitivities of the high-
level and low-level limiters are factory
set and cannot be changed.
Press button twice briefly to select
either of the following two response
sensitivities:
■ 0.5 µS/cm
■ 10 µS/cm
flashing
twice briefly
twice briefly