Press button once briefly to activate the
line editing mode.
If the reading of the calibrated conductivity
meter does not tally the value indicated by
the URB 1 the compensation gradient has
to be changed until the two values agree.
Example: With a gradient of 1.9 % /°C the
two readings tally.
Press button once briefly to select the
digit “1”.
Press button once briefly to enter the line
where the linear temperature compensation
[% /°C] can be adjusted.
The factory set gradient 2.1 [%/ °C] is
normally used for steam boilers operating
with constant pressure.
When the boiler is at full working pressure
compare the indicated value with the reading
of a calibrated conductivity meter – the two
values must tally.
Press button once briefly to move
the cursor one step further.
Basic Settings – continued –
Adjusting LIN (linear) temperature compensation – continued –
flashing
flashing
flashing
once briefly
once briefly
once briefly
once briefly